DS1200DC Series

1200 Watt Power Supplies (48 V DC Input)

The DS1200DC series bulk front end power supplies is the DC-input version of its DS1200 AC-input counterpart. Mechanically identical to the AC-input version, this product allows system operation from a Telco style 48 Vdc input. Rated at 1,200 watts, the power supply provides a main 12 V output and a 3.3 V or optional 5.5 V standby output. Active current sharing allows this power supply to be paralleled with the AC-input version, for use in battery back-up systems where both AC and DC input capabilities are required.

The main 12 V output can deliver up to 100 amps and stays within regulation down to zero load, making it perfect for feeding downstream DC-DC converters in systems that use distributed power architectures (DPA). Standard features include internal ORing FETs and an EEPROM for storing service data to facilitate efficient field replacement. The DS1200DC power supply is hot pluggable and ideal for fault tolerant and N+1 redundant applications.

This digitally-controlled power supply is PMBus™ compliant. A built-in I2C serial communication interface allows set-up, monitoring and control to be performed using Artesyn Embedded Power' universal PMBus graphical user interface.

Universal PMBus GUI Software Package

Datasheet Brochures Technical Documentation Print This Page
  • Total Max Power:
    1,200 W
  • Total Max Current:
    100 A
  • Input Voltage:
    -72 V to -40 V
  • Output Voltage:
    12 V to 12 V
  • Outputs:
    Single
  • Size (L x W x H):
    11.000" x 3.200" x 1.570"
  • Warranty:
    2 years
  • Operating Temperature:
    -10°C to +55°C

Electrical Specifications

  • Input
  • Output
  • Logic Control
  • Input Range: -40 to -70 VDC
  • Inrush Current: ETSI EN300 132-2 part 4.7 Compliant
  • Efficiency: > 92% typ at high line and 50% load
  • Conducted/Radiated EMI: GR-1089-CORE Issue 4
  • Hold-up Time: 12 mSec Min
  • Main DC Output: 12 VDC @ 100 A
  • Turn On Delay: 2 sec max, 5-50 mSec Monotonic Rise
  • Regulation: +/- 5%
  • Adjustment Range: +/- 5% on Main output using I2C
  • Stand-By: 3.3 Vsb @ 6 A or 5.0 Vsb @ 4 A
  • PS-Seated: TTL Logic LOW when supply is seated
  • PWR Good: TTL Logic HIGH when output in Regulation
  • AC OK: TTL Logic LOW when input is within Range
  • PS Kill: Open, output is off
  • PS ON: Pull Low to turn supply ON
  • CR-1089-CORE Issue 4 compliant
  • 1U x 2U Standard Form Factor
  • 21.71 W/cu-in
  • No Min Load Required
  • Hot Plug Operation
  • N+1 Redundant
  • Internal OR'ing FETs
  • Active Current Sharing
  • Shares with DS1200 (AC Input Unit)
  • Built-in Smart Fan
  • I2C communication Bus
  • PMBus compliant
  • EEPROM for FRU Data
  • Red/Green Bi-color LED status
  • Full Digital Control
  • NEBS Compliant

Let us help with your product selection